Mitsubishi Electronics MR-MC210 Sleep Apnea Machine User Manual


 
7 - 41
7. AUXILIARY FUNCTION
(2) Details concerning system status bits
Symbol Signal name Function details
SMPW Waiting for sampling
trigger
[Function]
Notifies concerning the status of waiting for sampling trigger.
[Operation]
<Conditions for turning on>
Turning on of sampling start signal (SMPS), and waiting for the sample trigger.
<Conditions for turning off>
• The sampling start signal (SMPS) is turned off.
• The trigger for the start sampling trigger axis is met.
SMPO Sampling is being
performed
[Function]
Notifies that sampling is now being performed.
[Operation]
<Conditions for turning on>
Turning on of sampling start signal (SMPS), and sampling is now being performed.
<Conditions for turning off>
• The sampling start signal (SMPS) is turned off.
• Sampling is completed.
SMPF Sampling is complete [Function]
Notifies that sampling was completed normally.
[Operation]
<Conditions for turning on>
Sampling is completed normally.
<Conditions for turning off>
The sampling start signal (SMPS) is turned off.
SMPE Sampling error [Function]
Notifies that sampling was not completed normally.
[Operation]
<Conditions for turning on>
• The sampling setting error occurs.
• The sampling item error occurs.
• The next page number of the sampling completion page number is the same as the
sampling read page number. (The data was not sampled in time.)
• The sampling start signal (SMPS) is turned on when the read sampled data completion
page number is -1.
• The page number 0 is designated from the page number other than 0 when the sampling
is being performed.
<Conditions for turning off>
The start sampling signal (SMPS) is turned off.
SWFIN Sampling setting
write complete
[Function]
Notifies that writing of the sampling setting was completed.
[Operation]
<Conditions for turning on>
The sampling setting write number and the setting value in the range are set correctly and
the sampling setting write command (SMPSW) is turned on.
<Conditions for turning off>
The sampling setting write command signal (SMPSW) is turned off.
SWEN Sampling setting
number error
[Function]
Notifies that the sampling setting number is incorrect.
[Operation]
<Conditions for turning on>
The sampling setting number is set incorrectly and the sampling setting write command
(SMPSW) is turned on.
<Conditions for turning off>