60 Micro Motion
®
Model 2400S Transmitters for PROFIBUS-DP
Optional Configuration
8.6.2 Checking and reporting event status
There are several ways that event status can be determined:
ProLink II automatically displays event information on the Informational panel of the Status
window, and also in the Output Levels window.
For PROFIBUS hosts using the EDD, event status is displayed in the Device menu (see
Figure C-6).
Using PROFIBUS bus parameters, event status is reported in the Diagnostic block, Index 9
(see Table D-4).
Note: You cannot view event status using a PROFIBUS host with the GSD.
Example
Define Discrete Event 1 to be active when the mass flow rate in forward
or backward direction is less than 2 lb/min or greater than 20 lb/min.
Additionally, if this occurs, all totalizers should be stopped.
Using ProLink II:
1. Specify lb/min as the mass flow unit. See Section 6.3.1.
2. Set Flow Direction to Absolute Value. See Section 8.5.
3. Select Event 1.
4. Configure:
Event Type = Out of Range
Process Variable (PV) = Mass Flow Rate
Low Setpoint (A) = 2
High Setpoint (B) = 20
5. In the Discrete Input panel, open the dropdown list for Start/Stop
All Totalization and select Discrete Event 1.
Using PROFIBUS bus parameters:
1. Specify lb/min as the mass flow unit. See Section 6.3.1.
2. Set Flow Direction to Absolute Value. See Section 8.5.
3. In the Diagnostic block, set the following attributes:
Discrete event index (Index 4) = 0
Discrete event action type (Index 5) = 3
Discrete event process variable (Index 8) = 0
Discrete event setpoint A (Index 6) = 2
Discrete event setpoint B (Index 7) = 20
Discrete event assignment (Index 83) = 57
Discrete event action code (Index 82) = 9