Emerson Process Management 2400S Pacemaker User Manual


 
Configuration and Use Manual 137
Troubleshooting
Measurement Performance DefaultsTroubleshootingCompensation
11.20.3 Drive gain problems
Problems with drive gain can appear in several different forms:
Saturated or excessive (near 100%) drive gain
Erratic drive gain (e.g., rapid shifting from positive to negative)
Negative drive gain
See Table 11-5 for a list of possible problems and remedies.
11.20.4 Low pickoff voltage
Low pickoff voltage can be caused by several problems. See Table 11-6.
Table 11-4 Sensor pickoff values
Sensor
(1)
(1) If your sensor is not listed, contact Micro Motion.
Pickoff value
ELITE
®
CMF sensors 3.4 mV peak-to-peak per Hz based on sensor flow tube frequency
F025, F050, F100 sensors 3.4 mV peak-to-peak per Hz based on sensor flow tube frequency
F200 sensors 2.0 mV peak-to-peak per Hz based on sensor flow tube frequency
H025, H050, H100 sensors 3.4 mV peak-to-peak per Hz based on sensor flow tube frequency
H200 sensors 2.0 mV peak-to-peak per Hz based on sensor flow tube frequency
R025, R050, or R100 sensors 3.4 mV peak-to-peak per Hz based on sensor flow tube frequency
R200 sensors 2.0 mV peak-to-peak per Hz based on sensor flow tube frequency
T-Series sensors 0.5 mV peak-to-peak per Hz based on sensor flow tube frequency
CMF400 I.S. sensors 2.7 mV peak-to-peak per Hz based on sensor flow tube frequency
Table 11-5 Drive gain problems, causes, and remedies
Cause Possible remedy
Excessive slug flow • See Section 11.14.
Cavitation or flashing • Increase inlet or back pressure at the sensor.
• If a pump is located upstream from the sensor, increase the distance
between the pump and sensor.
Plugged flow tube • Purge the flow tubes.
Mechanical binding of sensor tubes • Ensure sensor tubes are free to vibrate. Possible problems include:
- Pipe stress. Check for pipe stress and eliminate if present.
- Lateral tube shift due to hammer effect. If this is a possibility,
contact Micro Motion.
- Warped tubes caused by overpressurization. If this is a possibility,
contact Micro Motion.
Incorrect sensor type configured Verify sensor type configuration, then verify sensor characterization.
See Section 6.2.
Open drive or left pickoff sensor coil Contact Micro Motion.
Drive board or module failure, cracked flow tube,
or sensor imbalance
• Contact Micro Motion.