Emerson Process Management 2400S Pacemaker User Manual


 
Configuration and Use Manual 177
PROFIBUS Bus Parameters
Menus Display CodesBus ParametersDiagrams
83 DB_UNI_DE_
Assignment
USINT16 S R /W Discrete event assignment index
• 57 = Discrete Event 1
• 58 = Discrete Event 2
• 59 = Discrete Event 3
• 60 = Discrete Event 4
• 61 = Discrete Event 5
• 251 = None
84 DB_SYS_MasterReset USINT16 S R/W 0x0000 = No action
• 0x0001 = Perform master reset
85 SYS_AckAlarm USINT16 S R/W Write alarm index to acknowledge alarm. See
Table D-13 for alarm index codes
86 SYS_DriveCurrent FLOAT D (20 Hz) R Sensor drive current
Units: mA
87
(2)
DB_FRF_MV_Index USINT16 D (20 Hz) R/W Index of meter verification test record on
transmitter (0–19)
•0 = Newest
• 19 = Oldest
88
(2)
DB_FRF_MV_Counter USINT16 D (20 Hz) R Counter assigned to meter verification test
record
89
(2)
DB_FRF_MV_Status USINT16 D (20 Hz) R Meter verification test record: Test status
• Bit 7 = Pass/Fail
• Bits 6–4 = State
• Bits 3–0 = Abort code
90
(2)
DB_FRF_MV_Time USINT32 D (20 Hz) R Meter verification test record: Test start time
91
(2)
DB_FRF_MV_LPO_Nor
m
FLOAT D (20 Hz) R Meter verification test record: LPO stiffness
92
(2)
DB_FRF_MV_RPO_Nor
m
FLOAT D (20 Hz) R Meter verification test record: RPO stiffness
93
(2)
DB_FRF_MV_FirstRun_
Time
FLOAT D (20 Hz) R/W Meter verification scheduler: Hours until first
test
• Range: 1–1000
• 0 = No test scheduled
94
(2)
DB_FRF_MV_Elapse_Ti
me
FLOAT D (20 Hz) R/W Meter verification scheduler: Hours between
tests
• Range: 1–1000
• 0 = No recurring execution
95
(2)
DB_FRF_MV_Time_Left FLOAT D (20 Hz) R Meter verification scheduler: Hours until next
test
(1) Applies only to systems with the original version of the meter verification application.
(2) Applies only to systems with Smart Meter Verification.
Table D-4 Diagnostic block (Slot 3) continued
Index Name
Data
type
Memory
class Access Definition/Code/Comments