22 Model 2700 Transmitter with PROFIBUS-PA
Calibration
3.3 Performing a characterization
Characterizing a flowmeter involves entering parameters that are printed on the sensor tag.
3.3.1 Characterization parameters
The characterization parameters that must be entered depend on the sensor type: “T-Series” or
“Other,” as listed in Table 3-1. The “Other” category includes all Micro Motion sensors except
T-Series.
The characterization parameters are provided on the sensor tag. The format of the sensor tag varies
depending on your sensor’s date of purchase. See Figures 3-1 and 3-2 for illustrations of newer and
older sensor tags.
Table 3-1 Sensor characterization parameters
Characterization data EDD label
Bus parameter
index
Sensor type
T-S eri es Othe r
K1
(1)
(1) See the section entitled “Density calibration factors.”
K1 92 ✓✓
K2
(1)
K2 93 ✓✓
FD
(1)
FD 94 ✓✓
D1
(1)
D1 97 ✓✓
D2
(1)
D2 98 ✓✓
DT or TC
(1)
Density Temp Coeff (DT) 102 ✓✓
Flow cal
(2)
(2) See the section entitled “Flow calibration values.”
FD Value 99
FCF
(2)
FD Value 99
FT
(2)
FD Value 99
FTG FTG 103
FFQ FFQ 104
DTG DTG 105
DFQ1 DFQ1 106
DFQ2 DFQ2 107