Emerson Process Management Model 2700 Pacemaker User Manual


 
184 Model 2700 Transmitter with PROFIBUS-PA
Model 2700 PROFIBUS Block Parameters
F.4.11 Analog output block objects
Table F-16 shows the analog output block objects.
F.4.12 AO function block views
Table F-17 shows the views for the AO function blocks.
61 RESERVED
62 RESERVED
63 RESERVED
64 RESERVED
65 AO BLOCK VIEW 1
Table F-16 Analog output block objects
Slot/Index Element name Data type Size in bytes Value
Slot 11/Index 0 Reserved Unsigned 8 1 250 (default)
Block_Object Unsigned 8 1 02 (function block)
Parent_Class Unsigned 8 1 02 (output)
Class Unsigned 8 1 01 (A0)
DD_Refrence Unsigned 32 4 00 ,00, 00, 00 (reserved)
DD_Revision Unsigned 16 2 00 ,00 (reserved)
Profile Octet String 2 64 02 (compact class B)
Profile_Revision Unsigned 16 2 03 01 (3.01)
Execution_Time Unsigned 8 1 00 (for future use)
Number_Of_Parameters Unsigned 16 2 00 49 (max number of AO block parameters)
Address_of_View_1 Unsigned 16 2 AO1 09 65 (slot, index)
AO2 10 65 (slot, index)
Number_of_Views Unsigned 8 1 01 (1 view)
Table F-17 AO function block views
OD
Index
Parameter Mnemonic View 1 View 2 View 3 View 4
Standard Parameters
16 BLOCK_OBJECT
Table F-15 AO function block parameters (continued)
Index Parameter Mnemonic Definition Message
Ty pe
Data Type/
Structure
Size Store
/Rate
(HZ)
Default
Value
Access Enumerated List of
Values / Range
Modbus
Register / Coil