Emerson Process Management Model 2700 Pacemaker User Manual


 
Configuration and Use Manual 181
Model 2700 PROFIBUS Block Parameters
Status Bytes Block ParametersDiagnostic BytesProLink
F.4.8 Analog input block objects
Table F-13 shows the analog input block objects.
F.4.9 AI function block views
Table F-14 shows the views for the AI function blocks.
Table F-13 Analog input block objects
Slot/Index Element name Data type Size in bytes Value
Slot 11/Index 0 Reserved Unsigned 8 1 250 (default)
Block_Object Unsigned 8 1 02 (function block)
Parent_Class Unsigned 8 1 01 (input)
Class Unsigned 8 1 01 (AI)
DD_Refrence Unsigned 32 4 00 ,00, 00, 00 (reserved)
DD_Revision Unsigned 16 2 00 ,00 (reserved)
Profile Octet String 2 64 02 (compact class B)
Profile_Revision Unsigned 16 2 03 01 (3.01)
Execution_Time Unsigned 8 1 00 (for future use)
Number_Of_Parameters Unsigned 16 2 00 45 (max number of AI block parameters)
Address_of_View_1 Unsigned 16 2 AI1 01 61 (slot, index)
AI2 02 61 (slot, index)
AI3 03 61 (slot, index)
AI4 05 61 (slot, index)
Number_of_Views Unsigned 8 1 01 (1 view)
Table F-14 AI function block views
OD
Index
Parameter Mnemonic View 1 View 2 View 3 View 4
Standard Parameters
16 BLOCK_OBJECT
17 ST_REV 2
18 TAG_DESC
19 STRATEGY
20 ALERT_KEY
21 TARGET_MODE
22 MODE_BLK 3
23 ALARM_SUM 8
Overall sum of bytes in View Object 13
OD
Index
Parameter Mnemonic View 1 View 2 View 3 View 4
Standard Parameters
26 Out 5
61 Overall sum of bytes in View Object
(+ 13 Standard parameters bytes)
5+13