Emerson Process Management Model 2700 Pacemaker User Manual


 
Configuration and Use Manual 187
Model 2700 PROFIBUS Block Parameters
Status Bytes Block ParametersDiagnostic BytesProLink
F.4.14 Totalizer block objects
Table F-19 shows the totalizer block objects.
F.4.15 Totalizer function block views
Table F-20 shows the views for the totalizer function blocks.
51 RESERVED
52 Totalizer Selection
(DD Name: TOT Selection)
Selection of Totalizer
operation mode
SIMPLE Unsigned8 1 S 0 RW 0 – Standard (Profile
Specific)
1 – Internal Mass Total
2 – Internal Volume Total
3 – Internal Mass
Inventory
4 – Internal volume
Inventory
5 – Internal GSV Total
6 – Internal GSV
Inventory
7 – Internal API CorrVol
To tal
8 – Internal API CorrVol
Inventory
9 – Internal
ED_StdVolTotal
10 – Internal
ED_StdVolInv
11 – Internal
ED_NetMassTotal
12 – Internal
ED_NetMassInv
13 – Internal
ED_NetVolTotal
14 – Internal
ED_NetVolInv
R-2291
53 TOTALIZER BLOCK VIEW1
Table F-19 Totalizer block objects
Slot/Index Element name Data type Size in bytes Value
Slot 11/Index 0 Reserved Unsigned 8 1 250 (default)
Block_Object Unsigned 8 1 02 (function block)
Parent_Class Unsigned 8 1 05 (calculation class)
Class Unsigned 8 1 08 (TOT)
DD_Refrence Unsigned 32 4 00 ,00, 00, 00 (reserved)
DD_Revision Unsigned 16 2 00 ,00 (reserved)
Profile Octet String 2 64 02 (compact class B)
Profile_Revision Unsigned 16 2 03 01 (3.01)
Execution_Time Unsigned 8 1 00 (for future use)
Number_Of_Parameters Unsigned 16 2 00 37 (max number of totalizer block parameters)
Address_of_View_1 Unsigned 16 2 TOT1 04 53 (slot, index)
TOT2 06 53 (slot, index)
TOT3 07 53 (slot, index)
TOT4 08 53 (slot, index)
Number_of_Views Unsigned 8 1 01 (1 view)
Table F-18 Totalizer block parameters (continued)
Index Parameter Mnemonic Definition Message
Ty pe
Data Type/
Structure
Size Store
/Rate
(HZ)
Default
Value
Access Enumerated List of
Values / Range
Modbus
Register /
Coil