Emerson Process Management Model 2700 Pacemaker User Manual


 
Configuration and Use Manual 11
Startup
Startup ConfigurationCalibrationBefore You Begin
Note: Set the I/O mode in the Physical Block before loading the GSD file.
2.5.1 Overriding the status byte format
Each I/O mode has a default status byte format – classic or condensed. To override this default:
With the GSD, set the Condensed Status parameterization bit to either 1 (for condensed status)
or 0 (for classic status).
With the EDD or bus parameters, use the menu flowcharts in Figure 2-3.
Figure 2-3 Status byte format
2.6 Configuring the totalizer block mode
The behavior of the four totalizer function blocks can be configured in two ways:
Standard, which provides standard PROFIBUS totalizer function block behavior.
In this mode, the totalizer block will integrate whatever data it receives. The Out value of a
totalizer in this mode has no relationship to the totalizer data reported by the transducer block,
ProLink II, or the display.
Any of the values in Table 2-5, which cause the totalizer function block to pass through the
specified totalizer value from the transducer block.
Micro Motion recommends using one of these modes, because the totalizer block output will
be more accurate and will match readings taken with ProLink II and the display.
To configure the totalizer block mode:
With the EDD or bus parameters, refer to the menu flowcharts in Figure 2-4.
With the display, refer to the menu flowcharts in Figure B-16.
Table 2-4 PROFIBUS GSD file names
Identification number GSD file name
Profile specific PA139742.GSD
Manufacturer specific V3x_057A.gsd
Block: Physical Block 1 (Slot 0)
Index 43 (Condensed status diagnostics)
Status byte format
EDD Bus parameters