Procedure
Set Discrete Output Fault Action as desired.
The default setting is None.
Options for Discrete Output Fault Action
Options for Discrete Output Fault ActionTable 6-10:
Label
Discrete output behavior
Polarity=Active High Polarity=Active Low
Upscale
• Fault: discrete output is ON
(site-specific voltage)
• No fault: discrete output is con-
trolled by its assignment
• Fault: discrete output is OFF
(0 V)
• No fault: discrete output is con-
trolled by its assignment
Downscale
• Fault: discrete output is OFF
(0 V)
• No fault: discrete output is con-
trolled by its assignment
• Fault: discrete output is ON
(site-specific voltage)
• No fault: discrete output is con-
trolled by its assignment
None (default) Discrete output is controlled by its assignment
Fault indication with the discrete output
To indicate faults via the discrete output, set parameters as follows:
• Discrete Output Source = Fault
• Discrete Output Fault Action = None
Note
If Discrete Output Source is set to Fault and a fault occurs, the discrete output is always ON. The setting
of Discrete Output Fault Action is ignored.
6.5 Configure events
An event occurs when the real-time value of a user-specified process variable moves past a
user-defined setpoint. Events are used to provide notification of process changes or to
perform specific transmitter actions if a process change occurs.
Your transmitter supports two event models:
• Basic event model
• Enhanced event model
Integrate the meter with the control system
Configuration and Use Manual 89