6.3.4 Configure Frequency Output Fault Action and Frequency
Output Fault Level
ProLink II ProLink > Configuration > Frequency/Discrete Output > Frequency > Freq Fault Action
ProLink > Configuration > Frequency/Discrete Output > Frequency > Freq Fault Level
ProLink III Device Tools > Configuration > Fault Processing
Field Communicator Configure > Manual Setup > Inputs/Outputs > Frequency Output > FO Fault Parameters > FO
Fault Action
Configure > Manual Setup > Inputs/Outputs > Frequency Output > FO Fault Parameters > FO
Fault Level
Overview
Frequency Output Fault Action controls the behavior of the frequency output if the transmitter
encounters an internal fault condition.
Note
For some faults only: If Last Measured Value Timeout is set to a non-zero value, the transmitter will not
implement the fault action until the timeout has elapsed.
Procedure
1.
Set Frequency Output Fault Action as desired.
The default value is Downscale (0 Hz).
2. If you set Frequency Output Fault Action to Upscale, set Frequency Fault Level to the desired
value.
The default value is 15000 Hz. The range is 10 to 15000 Hz.
Options for Frequency Output Fault Action
Options for Frequency Output Fault ActionTable 6-7:
Label Frequency output behavior
Upscale
Goes to configured Upscale value:
Range: 10 Hz to 15000 Hz
Default: 15000 Hz
Downscale
0 Hz
Internal Zero
0 Hz
None (default) Tracks data for the assigned process variable; no fault action
Integrate the meter with the control system
Configuration and Use Manual 83