The GSV flow measurement parameters include:
•
Volume Flow Type
•
Standard Gas Density
•
Gas Standard Volume Flow Measurement Unit
•
Gas Standard Volume Flow Cutoff
Restriction
You cannot implement both liquid volume flow and gas standard volume flow at the same time. You
must choose one or the other.
4.3.1 Configure Volume Flow Type for gas applications
ProLink II ProLink > Configuration > Flow > Vol Flow Type
ProLink III Device Tools > Configuration > Process Measurement > Flow
Field Communicator Configure > Manual Setup > Measurements > GSV > Volume Flow Type
Overview
Volume Flow Type controls whether liquid or gas standard volume flow measurement is
used.
Procedure
Set Volume Flow Type to Gas Standard Volume.
4.3.2 Configure Standard Gas Density
ProLink II ProLink > Configuration > Flow > Std Gas Density
ProLink III Device Tools > Configuration > Process Measurement > Flow
Field Communicator Configure > Manual Setup > Measurements > GSV > Gas Ref Density
Overview
The Standard Gas Density value is used to convert the measured flow data to the standard
reference values.
Prerequisites
Ensure that Density Measurement Unit is set to the measurement unit you want to use for
Standard Gas Density.
Procedure
Set Standard Gas Density to the standard reference density of the gas you are measuring.
Configure process measurement
34 Micro Motion
®
Model 1500 Transmitters with Analog Outputs