Emerson 1500 Pacemaker User Manual


 
Tip
In typical installations, burst mode is disabled. Enable burst mode only if another device on
the network requires burst mode communication.
4. (Optional) Configure HART Variables.
Configure burst parameters
ProLink II ProLink > Configuration > Device > Burst Setup
ProLink III Device Tools > Configuration > Communications > Communications (HART)
Field Communicator Configure > Manual Setup > Inputs/Outputs > Communications > Set Up Burst Mode
Overview
Burst mode is a mode of communication during which the transmitter regularly
broadcasts HART digital information over the mA output. The burst parameters control
the information that is broadcast when burst mode is enabled.
Tip
In typical installations, burst mode is disabled. Enable burst mode only if another device on the
network requires burst mode communication.
Procedure
1.
Enable Burst Mode.
2. Set Burst Mode Output as desired.
Label
DescriptionProLink II ProLink III
Field Communi-
cator
Primary Variable Source (Primary
Variable)
PV
The transmitter sends the primary
variable (PV) in the configured
measurement units in each burst
(e.g., 14.0 g/sec, 13.5 g/sec,
12.0 g/sec).
PV current & % of
range
Primary Variable
(Percent Range/
Current)
% range/current
The transmitter sends the PV’s per-
cent of range and the PV’s actual
mA level in each burst (e.g., 25%,
11.0 mA).
Integrate the meter with the control system
94 Micro Motion
®
Model 1500 Transmitters with Analog Outputs