Emerson 1500 Pacemaker User Manual


 
Postrequisites
For each channel that you configured, perform or verify the corresponding input or output
configuration. When the configuration of a channel is changed, the channel’s behavior will
be controlled by the configuration that is stored for the selected input or output type, and
the stored configuration may not be appropriate for your process.
After verifying channel and output configuration, return the control loop to automatic
control.
6.2 Configure the mA output
The mA output is used to report the configured process variable. The mA output
parameters control how the process variable is reported. Your transmitter has one mA
output: Channel A.
The mA output parameters include:
mA Output Process Variable
Lower Range Value (LRV) and Upper Range Value (URV)
AO Cutoff
Added Damping
AO Fault Action and AO Fault Value
Important
Whenever you change an mA output parameter, verify all other mA output parameters before
returning the flowmeter to service. In some situations, the transmitter automatically loads a set of
stored values, and these values may not be appropriate for your application.
6.2.1 Configure mA Output Process Variable
ProLink II ProLink > Configuration > Analog Output > Primary Output > PV Is
ProLink III Device Tools > Configuration > I/O > Outputs > mA Output
Field Communicator Configure > Manual Setup > Inputs/Outputs > mA Output > Primary Variable
Overview
Use mA Output Process Variable to select the variable that is reported over the mA output.
Prerequisites
If you plan to configure the output to report volume flow, ensure that you have set
Volume Flow Type as desired: Liquid or Gas Standard Volume.
If you are using the HART variables, be aware that changing the configuration of mA
Output Process Variable will change the configuration of the HART Primary Variable
(PV) and the HART Tertiary Variable (TV).
Integrate the meter with the control system
72 Micro Motion
®
Model 1500 Transmitters with Analog Outputs