Milliamp output problems and recommended actions (continued)Table 10-6:
Problem Possible causes Recommended actions
mA output consis-
tently out of range
Incorrect process variable or units assigned
to output
Fault condition if fault action is set to up-
scale or downscale
LRV and URV are not set correctly
Verify the output variable assignments.
Verify the measurement units configured
for the output.
Check the Fault Action settings. See
Section 10.19.
Check the settings of Upper Range Value and
Lower Range Value. See Section 10.18.
Check the mA output trim. See
Section 10.17.
Consistently incorrect
mA measurement
Loop problem
Output not trimmed correctly
Incorrect flow measurement unit config-
ured
Incorrect process variable configured
LRV and URV are not set correctly
Check the mA output trim. See
Section 10.17.
Verify that the measurement units are con-
figured correctly for your application.
Verify the process variable assigned to the
mA output.
Check the settings of Upper Range Value and
Lower Range Value. See Section 10.18.
mA output correct at
lower current, but in-
correct at higher cur-
rent
mA loop resistance may be set too high Verify that the mA output load resistance
is below maximum supported load (see
the installation manual for your transmit-
ter).
10.7 Frequency output problems
Troubleshooting
Configuration and Use Manual 161