Emerson 1500 Pacemaker User Manual


 
Options for Enhanced Event Action
Options for Enhanced Event ActionTable 6-11:
Action Label
ProLink II ProLink III Field Communicator
Standard
None (default)
None None None
Start sensor zero
Start Sensor Zero Start Sensor Zero Perform auto zero
Start/stop all totalizers
Start/Stop All Totalization Start/Stop All Totalization Start/stop totals
Reset mass total
Reset Mass Total Reset Mass Total Reset mass total
Reset volume total
Reset Volume Total Reset Volume Total Reset volume total
Reset gas standard volume
total
Reset Gas Std Volume Total Reset Gas Std Volume Total Reset gas standard volume total
Reset all totals
Reset All Totals Reset All Totals Reset totals
Meter verification
Start meter verification test
Start Meter Verification Start Meter Verification
Not available
CAUTION!
Before assigning actions to an enhanced event or discrete input, check the status of the event
or the remote input device. If it is ON, all assigned actions will be performed when the new
configuration is implemented. If this is not acceptable, wait until an appropriate time to assign
actions to the event or discrete input.
6.6 Configure digital communications
The digital communications parameters control how the transmitter will communicate
using digital communications.
Your transmitter supports the following types of digital communications:
HART/Bell 202 over the primary mA terminals
Modbus/RS-485 over the RS-485 terminals
Modbus RTU via the service port
Note
The service port responds automatically to a wide range of connection requests. It is not
configurable.
Integrate the meter with the control system
92 Micro Motion
®
Model 1500 Transmitters with Analog Outputs