• If the mA output reading was significantly off (±200 microamps), or if at any step the
reading was faulty, verify the wiring between the transmitter and the remote device,
and try again.
• If the discrete output reading is reversed, check the setting of Discrete Output Polarity.
10.12.2 Perform loop tests using ProLink III
Prerequisites
Before performing a loop test, configure the channels for the transmitter inputs and
outputs that will be used in your application.
Follow appropriate procedures to ensure that loop testing will not interfere with existing
measurement and control loops.
ProLink II must be running and must be connected to the transmitter.
Procedure
1.
Test the mA output(s).
a. Choose Device Tools > Diagnostics > Testing > mA Output 1 Test or Device Tools >
Diagnostics > Testing > mA Output 2 Test.
b. Enter 4 in Fix to:.
c. Click Fix mA.
d. Read the mA current at the receiving device and compare it to the transmitter
output.
The readings do not need to match exactly. If the values are slightly different,
you can correct the discrepancy by trimming the output.
e. Click UnFix mA.
f. Enter 20 in Fix to:.
g. Click Fix mA.
h. Read the mA current at the receiving device and compare it to the transmitter
output.
The readings do not need to match exactly. If the values are slightly different,
you can correct the discrepancy by trimming the output.
i. Click UnFix mA.
2. Test the frequency output(s).
a. Choose Device Tools > Diagnostics > Testing > Frequency Output Test.
b. Enter the frequency output value in Fix to.
c. Click Fix FO.
d. Read the frequency signal at the receiving device and compare it to the
transmitter output.
Troubleshooting
166 Micro Motion
®
Model 1500 Transmitters with Analog Outputs