Model 2200S Transmitters
Operating the Transmitter
8.6.4 With the Communicator
The Communicator allows you to perform the following actions related to status alarms:
View a list of active status alarms
Acknowledge a single status alarm
Acknowledge all status alarms at once
View the alarm event log
To view all active Fault and Information alarms, you can use either of the following methods:
Select
Diag/Service > Test/Status > View Status, then press OK to cycle through a list of
active alarms.
Select
Process Variables > View Status, then press OK to cycle through a list of active
alarms.
Note: The transmitter automatically filters out Ignore alarms.
To acknowledge a single alarm, select
Diag/Service > Alarm Config > Acknowledge Selected
Alarm
, then enter the alarm code.
To acknowledge all alarms with one action, select
Diag/Service > Perform Diagnostic Action >
Acknowledge All Alarms
. You do not need to enter alarm codes.
The alarm event log contains one record for each of the fifty most recent active Fault and Information
status alarms. Ignore alarms are not listed. Each record contains:
The alarm code
The alarm status (e.g., cleared but unacknowledged)
The timestamp, which is the number of seconds that this alarm has been active, while the
transmitter has been powered on.
Note: The timestamp value is not reset during a transmitter power cycle. To reset this value, you must
perform a master reset or use a Modbus command. Contact Micro Motion customer support.
To view records in the alarm event log, select
Diag/Service > Alarm Config > Alarm Event Log.
To clear the alarm log, select
Diag/Service > Perform Diagnostic Action > Reset Alarm Log.
8.7 Using the totalizers and inventories
The totalizers keep track of the total amount of mass or volume measured by the transmitter over a
period of time. The totalizers can be started and stopped, and the totals can be viewed and reset.
The inventories track the same values as the totalizers, but inventory values can be reset separately.
This allows you to keep a running total of mass or volume across multiple resets.
8.7.1 Viewing current totals for totalizers and inventories
You can view current totals for the totalizers and inventories with the display, ProLink II, or the
Communicator.
With the display
Note: You cannot view current totals with the display unless the total has been configured as a display
variable. See Section 5.2.3.