70 Micro Motion
®
Model 2200S Transmitters
Integrating the Meter with the Control System
Table 6-7 Burst Mode Output options
Parameter
DefinitionProLink II label Communicator label
Primary variable PV The transmitter repeats the primary variable (in measurement
units) in each burst (e.g., 14.0 g/s, 13.5 g/s, 12.0 g/s).
PV current & % of range % range/current The transmitter sends the PV’s percent of range and the PV’s
actual mA level in each burst (e.g., 25%, 11.0 mA).
(1)
(1) If the Micro Motion adapter-barrier is installed, the mA value will be converted to the 4–20 mA output scale at the adapter-barrier.
Dynamic vars & PV
current
(2)
(2) This burst mode setting is typically used with the HART Tri-Loop
signal converter. See the Tri-Loop manual for additional
information.
Process
variables/current
The transmitter sends PV, SV, TV, and quaternary variable (QV)
values in measurement units and the PV’s actual milliamp
reading in each burst (e.g., 50 lb/min, 23
°
C, 50 lb/min,
0.0023 g/cm
3
, 11.8 mA).
(1)
Transmitter vars Fld dev var The transmitter sends four process variables in each burst. See
Step 4.