Emerson 2200S Pacemaker User Manual


 
Configuration and Use Manual 77
Testing and Moving to Production
Operation AppendicesMaintenance and TroubleshootingCommissioning
Figure 7-5 Communicator – Loop test procedure
1 Fix Analog Out 1
Set mA measurement point
Correct?
Loop test successful
END to unfix
Check output wiring
Troubleshoot receiving device
Yes No
4 mA
20 mA
Other
On-Line Menu >
3 Diag/Service >
2 Loop test