Emerson 2200S Pacemaker User Manual


 
106 Micro Motion
®
Model 2200S Transmitters
Troubleshooting
10.10 I/O problems
If you are experiencing problems with the mA output, use Table 10-2 to identify an appropriate
remedy. Simulation mode may also be helpful (see Section 10.11).
Table 10-2 I/O problems and remedies
Symptom Possible cause Possible remedy
No output
Loop test failed
Power supply problem • Check power supply and power supply wiring.
See Section 10.14.1.
mA output < 4 mA Process condition below LRV • Verify process.
• Change the LRV. See Section 6.2.2.
Fault condition if fault action is set to
internal zero or downscale
• Check the fault action settings to verify
whether or not the transmitter is in a fault
condition. See Section 6.2.5.
• If a fault condition is present, see Section 10.8.
Open in wiring • Verify all connections.
Bad mA receiving device Check the mA receiving device or try another
mA receiving device. See Section 10.16.
• Perform output simulation to locate the
problem. See Section 10.11
.
Bad output circuit • Measure DC voltage across output to verify
that output is active.
• Perform output simulation to locate the
problem. See Section 10.11
.
Output not powered Check transmitter wiring. See the transmitter
installation manual.
Constant mA output Non-zero HART address • Set HART address to 0 or enable the Loop
Current Mode parameter. See Section 10.19.
Output is fixed in a test mode • Exit output from test mode. See Section 7.3.
Zero calibration failure Cycle power.
• Stop flow and rezero. See Section 7.2.
mA output consistently out of
range
Fault condition if fault indicator is set to
upscale or downscale
• Check the fault indicator settings to verify
whether or not the transmitter is in a fault
condition. See Section 6.2.5.
• If a fault condition is present, see Section 10.8.
LRV and URV not set correctly Check the LRV and URV. See Section 10.20.
Consistently incorrect mA
measurement
Scaling mismatch between transmitter
and host.
• Ensure that the host is scaled for either 12–20
mA input or 4–20 mA input, as appropriate to
your installation. See Section 8.3.
Output not trimmed correctly • Trim the output. See Section 7.4.
Incorrect flow measurement unit
configured
• Verify flow measurement unit configuration.
See Section 10.20.
Incorrect process variable configured Verify process variable assigned to mA output.
See Section 6.2.1.
LRV and URV not set correctly Check the LRV and URV. See Section 10.18.
mA reading correct at low
currents but wrong at higher
currents
mA loop resistance may be too high • Verify mA output load resistance is below
maximum supported load (see installation
transmitter manual).