Troubleshooting
A008 Density Outside
Limits
The measured density has
exceeded 0–10 g/cm
3
• If other alarms are present (typically, A003, A006, A102, or
A105), resolve those alarm conditions first. If the A008
alarm persists, continue with the suggestions here.
• Verify process. Check for air in the flow tubes, tubes not
filled, foreign material in tubes, or coating in tubes.
• Check for slug flow. See Section 10.17.
• Check the sensor circuitry. See Section 10.24.
• Verify calibration factors in transmitter configuration. See
Section 4.2.
• Check the test points. See Section 10.23.
• If the problem persists, contact Micro Motion.
Density Overrange
A009 Transmitter
Initializing/Warming
Up
Transmitter in power-up
mode.
• Allow the flowmeter to warm up (approximately 30
seconds). The error should disappear once the flowmeter
is ready for normal operation.
• If alarm does not clear, make sure that the sensor is
completely full or completely empty.
• Check the sensor circuitry. See Section 10.24.
Transmitter
Initializing/Warming
Up
A010 Calibration Failure Mechanical zero: The
resulting zero was greater
than 3 μs.
Temperature/Density Cals:
many possible causes.
• If alarm appears during a transmitter zero, ensure that
there is no flow through the sensor, then retry.
• Cycle power to the flowmeter, then retry.
• If appropriate, restore the factory zero to return the
flowmeter to operation.
Calibration Failure
A011 Excess Calibration
Correction, Zero
too Low
See A10 Ensure that there is no flow through the sensor, then retry.
• Cycle power to the flowmeter, then retry.
• If appropriate, restore the factory zero to return the
flowmeter to operation.
Zero Too Low
A012 Excess Calibration
Correction, Zero
too High
See A10 Ensure that there is no flow through the sensor, then retry.
• Cycle power to the flowmeter, then retry.
• If appropriate, restore the factory zero to return the
flowmeter to operation.
Zero Too High
A013 Process too Noisy
to Perform Auto
Zero
See A10. • Remove or reduce sources of electromechanical noise,
then retry. Sources of noise include:
- Mechanical pumps
- Pipe stress at sensor
- Electrical interference
- Vibration effects from nearby machinery
• Cycle power to the flowmeter, then retry.
• If appropriate, restore the factory zero to return the
flowmeter to operation.
Zero Too Noisy
A014 Transmitter Failed Many possible causes. • Cycle power to the flowmeter.
• The transmitter might need service. Contact Micro Motion.
Transmitter Failed
A016 Line RTD
Temperature
Out-Of-Range
The value computed for
the resistance of the Line
RTD is outside limits
• Check the sensor RTD circuitry. See Section 10.24.
• Verify that process temperature is within range of sensor
and transmitter.
• If the problem persists, contact Micro Motion.
Line RTD
Temperature
Out-of-Range
A020 Calibration Factors
Unentered
The flow calibration factor
and/or K1 has not been
entered since the last
master reset.
• Check the characterization. Specifically, verify the FCF
and K1 values. See Section 4.2.
• If the problem persists, contact Micro Motion.
Calibration Factors
Unentered
(FlowCal)
Table 10-3 Status alarms and remedies continued
Alarm
code
Communicator
Cause Suggested remedyProLink II