Emerson 2200S Pacemaker User Manual


 
74 Micro Motion
®
Model 2200S Transmitters
Testing and Moving to Production
Figure 7-2 Communicator – Flowmeter zero procedure
Figure 7-3 ProLink II – Flowmeter zero procedure
Modify zero time if
required
Perform auto zero
Auto Zero Failed Auto Zero Complete
OK
1 Auto zero
Calibration in Progress
message
OK
On-Line Menu >
3 Diag/Service >
3 Calibration
Troubleshoot
Modify zero time
if required
Calibration
Failure LED
Calibration in Progress
LED turns red
Green
Troubleshoot
Red
Perform Auto Zero
Done
ProLink >
Calibration >
Zero Calibration
Wait until Calibration in
Progress LED turns green