58 Micro Motion
®
Model 2200S Transmitters
Configuring Operational Parameters
Configuration
To configure status alarm severity:
• Using the Communicator, select
Diag/Service > Config Alarms > Write Severity.
• Using ProLink II, click ProLink > Configuration > Alarm.
Note: You cannot configure status alarm severity with the display.
5.3.2 Last measured value (LMV) timeout
By default, the transmitter immediately performs the configured mA output fault action as soon as a
fault is detected.
• For certain faults only, you can delay the mA fault action by changing the Last Measured
Value Timeout (LMV Timeout) to a nonzero value. During the timeout period, the transmitter
continues to report its last valid measurement.
• For other faults, the mA fault action is performed immediately.
Note: For all faults, the digital communications fault action is performed immediately.
For information on which faults are affected by LMV Timeout, see Table 5-5.
Configuration
To configure LMV Timeout:
• Using the Communicator, select
Detailed Setup > Config Outputs > Channel Setup >
AO Setup > AO1 Fault Setup
.
• Using ProLink II, click
ProLink > Configuration > Analog Output.
Note: You cannot configure LMV Timeout with the display.
5.4 Configuring sensor parameters
The sensor parameters are used to describe the sensor component of your flowmeter. They are not
used in transmitter processing, and are not required. The following sensor parameters can be
configured:
• Serial number
• Sensor material
• Liner material
•Flange
Configuration
To configure sensor parameters:
• Using the Communicator, select
Detailed Setup > Device Information.
• Using ProLink II, click
ProLink > Configuration > Sensor.
Note: You cannot configure sensor parameters with the display.