Mitsubishi Q68TD-G-H02 Thermometer User Manual


 
3 - 60
3.4 Buffer Memory
3.4.26 Disconnection state conversion setting (Un\G164, Un\G165) (Q68TD-G-H01only)
3
SPECIFICATIONS
3.4.26 Disconnection state conversion setting (Un\G164, Un\G165)
(Q68TD-G-H01only)
When disconnection state is checked, a value stored into CH Measured temperature
value (Un\G11toUn\G18) is set. (Refer to Section 3.2.3)
The value to be stored is selected from “Up scale”, “Down scale” or “Given value”.
(1) Setting methods
(a) Set the value to be stored in buffer memory.
Figure 3.39 Setting of Disconnection state conversion setting (Un\G164, Un\G165)
The value to be stored into CH Measured temperature value (Un\G11toUn\G18)
in the disconnection state check changes as follows, depending on the setting
value.
1) Up scale (0
H)
Up-scale of the range currently set is stored.
2) Down scale (1
H)
Down-scale of the range currently set is stored.
3) Given value (2
H)
The value set in CH Conversion setting for disconnection state value
(Un\G166toUn\G173) is stored.
(b) Turn on Operating condition setting request (Y9) to activate the setting.
(2) Default value
All channels are set to “Down scale” (1111H).
POINT
If a value out of the setting range is set, the module operates with the default
setting, “Down scale”(1
H).
0
H
1
H
2
H
b15 b12 b11 b8 b7 b4b3 b0
CH8 CH7 CH6 CH5
CH4 CH3 CH2 CH1
Un\G164 (Disconnection state
conversion setting CH1 to CH4)
Un\G165 (Disconnection state
conversion setting CH5 to CH8)
Measured temperature value when
confirming disconnection state
Up scale
Down scale
Given value
Setting
value
to
to
to
to