7 - 14
7.3 Online Module Change Procedure
7.3.3 When user range setting is used and initial setting was made with GX Configurator-TI (other system
7
ONLINE MODULE CHANGE
(b) Click the button to enable a module change.
Figure 7.24 "Online module change" screen
If the following error screen appears, the user range cannot be saved.
Click the button, and perform the operation in Section 7.3.4 (2)(c)
and later.
Figure 7.25 Error screen
(c) After confirming that the "RUN" LED of the module has turned off, remove the
connector and dismount the module.
POINT
Always dismount the module. If you execute mounting confirmation without
dismounting the module, the module will not start properly and the "RUN" LED will
not be lit.
(3) Mounting of new module
(a) Mount the dismounted module and new module to the other system.
(b) Using the G(P).OGLOAD instruction, save the user range setting values to the
CPU device. Refer to Appendix 2.3 for the G(P).OGLOAD instruction.
(c) Using the G(P).OGSTOR instruction, restore the user range setting values to the
module. Refer to Appendix 2.4 for the G(P).OGSTOR instruction.
(d) Dismount a new module from the other system, mount it to the slot from where the
old module was dismounted in the original system, and install the connector.