3.2 Function List
3.2.1 Temperature conversion system
3 - 11
1
OVERVIEW
2
SYSTEM
CONFIGURATION
3
SPECIFICATIONS
4
SETUP AND
PROCEDURES BEFORE
OPERATION
5
UTILITY PACKAGE (GX
CONFIGURATOR-TI)
6
PROGRAMMING
7
ONLINE MODULE
CHANGE
8
TROUBLESHOOTING
[Example 1: Measured temperature value when the temperature input value is changed
from 250.0
to 260.0 ]
When the time constant setting is 3200ms (3.2s), the measured temperature value
changes as indicated below.
At 3200ms (3.2s) after the temperature input value is changed to 260.0 , the
measured temperature value reaches 63.2% (256.3 )of the value when sampling
processing is selected.
Figure 3.4 Measured temperature value when the temperature input value is changed from 250.0 to 260.0
[Example2: Measured temperature value when the change of temperature input value is a
waveform with ringing]
The changes of measured temperature values when the time constant setting is
1280ms(1.28s), 640ms(0.64s) or the moving average processing is 4 times are shown
below.
Figure 3.5 Measured temperature value when the change of temperature input value is a waveform with ringing
0 3200
250.0
252.0
254.0
256.0
258.0
260.0
262.0 2620
2600
2500
2520
2540
2560
2580
Temperature input value
Measured temperature value
Elapsed time (ms)
Temperature input value ( )
Measured temperature value
0
2620
2600
2500
2520
2540
2560
2580
Elapsed time (ms)
1000
2000
3000
4000
5000
6000
7000
250.0
252.0
254.0
256.0
258.0
260.0
262.0
Temperature input value
Measured temperature value
(Moving average processing 4 times)
Measured temperature value
(Time constant setting 640ms)
Measured temperature value
(Time constant setting 1280ms)
Temperature input value ( )
Measured temperature value