3.4.25 Conversion setting for disconnection detection (Un\G164,
Un\G165) (Q68TD-G-H02 only)
When disconnection is detected, a value stored into CH Measured temperature value
(Un\G11toUn\G18) is set. (Refer to Section 3.2.2)
The value to be stored is selected from “Up scale”, “Down scale” or “Given value”.
(1) Setting methods
(a) Set the value to be stored into buffer memory.
Figure 3.38 Setting of Conversion setting for disconnection detection (Un\G164, Un\G165)
The value to be stored into CH Measured temperature value (Un\G11toUn\G18)
changes as follows, depending on the setting value.
1) Up scale (0
H)
Up-scale of the range currently set is stored.
2) Down scale (1
H)
Down-scale of the range currently set is stored.
3) Given value (2
H)
The value set in CH Conversion setting value for disconnection detection
(Un\G166toUn\G173) is stored.
(b) Turn on Operating condition setting request (Y9) to activate the setting.
(2) Default value
All channels are set to “Down scale” (1111H).
POINT
If a value out of the setting range is set, the module operates with the default
setting, “Down scale”(1
H).
b15 b12 b11 b8 b7 b4b3 b0
CH8 CH7 CH6 CH5
CH4 CH3 CH2 CH1
Un\G164 (Conversion setting for
disconnection detection CH1-4)
Un\G165 (Conversion setting for
disconnection detection CH5-8)
Measured temperature value at the
time of disconnection detection
Up scale
Down scale
Given value
Setting
value
to
to
to
to
0
H
1
H
2
H