Mitsubishi Q68TD-G-H02 Thermometer User Manual


 
6
PROGRAMMING
6.3 Using Programs on Remote I/O Network
6.3.2 Program example when GX Configurator-TI is used
6 - 18
1
OVERVIEW
2
SYSTEM
CONFIGURATION
3
SPECIFICATIONS
4
SETUP AND
PROCEDURES BEFORE
OPERATION
5
UTILITY PACKAGE (GX
CONFIGURATOR-TI)
6
PROGRAMMING
7
ONLINE MODULE
CHANGE
8
TROUBLESHOOTING
6.3.2 Program example when GX Configurator-TI is used
(1) List of devices
(2) GX Developer operation
(a) CPU parameter setting
Network range assignment:
Figure 6.19 Network range assignment setting screen
Table 6.8 List of devices
Device Function
W0 Device that Conversion completion flag is written by auto refresh
W1 Device that CH1 Measured temperature value is written by auto refresh
W2 Device that CH2 Measured temperature value is written by auto refresh
W3 Device that CH3 Measured temperature value is written by auto refresh
W4 Device that Error code is written by auto refresh
W5 Device that Warning output flag (Process alarm) is written by auto refresh
W6 Device that Warning output flag (Rate alarm) is written by auto refresh
W7 Device that Disconnection detection flag is written by auto refresh
D11 CH1Measured temperature value
D12 CH2Measured temperature value
D13 CH3Measured temperature value
X20
Device that user turns on to start reading
measured temperature values
QX10(X20 to X2F)
X21
Device that user turns on to reset a disconnection
detection state
X22 Device that user turns on to reset an error
Y30 to Y3B Error code display (BCD 3 digits) QY10(Y30 to Y3F)
X1000 Module ready
Q68TD-G-H02(X/Y1000 to X/Y100F)
X100C Disconnection detection signal
X100F Error flag
Y100F Error clear request
Network type : MNET/H (Remote master)
Starting I/O No. : 0000
H
Network No. : 1
Total stations : 1
Mode : Online