Mitsubishi Q68TD-G-H02 Thermometer User Manual


 
6 - 13
6.2 Using Programs in Normal System Configuration
6.2.3 Program example when GX Configurator-TI is not used
6
PROGRAMMING
* 1 Un\G0: Conversion enable/disable setting (Refer to Section 3.4.2)
Figure 6.13 Conversion enable/disable setting
* 2 Un\G24: Averaging processing selection (CH1 to CH4) (Refer to Section 3.4.9)
Figure 6.14 Averaging processing selection (CH1 to CH4)
* 3 Un\G46: Warning output enable/disable setting (Refer to Section 3.4.13)
Figure 6.15 Warning output enable/disable setting
Un\G98 CH2 Process alarm lower lower limit value 2000
Values required to use CH2
Process alarm are set.
Un\G99 CH2 Process alarm lower upper limit value 2050
Un\G100 CH2 Process alarm upper lower limit value 2950
Un\G101 CH2 Process alarm upper upper limit value 3000
Un\G128 CH3 Rate alarm warning detection period 3
Values required to use CH3
Process alarm are set.
Un\G138 CH3 Rate alarm upper limit value 50
Un\G139 CH3 Rate alarm lower limit value -50
Table 6.5 List of buffer memory addresses to be used
Address Description
Setting
value
Remarks
H
00F8
10001111
CH4 to CH8: 1
(Disable)
CH1 to CH3: 0
(Enable)
b7 b6 b5 b4 b3 b2 b1 b0
CH8CH7CH6CH5 CH4CH3CH2CH1
H
0420
0H (Sampling processing)
2
H (Count average)
4
H (Primary delay filter)
CH4 CH3 CH2 CH1
H
FBFD
10111111
Rate alarm setting
b7 b6 b5 b4 b3 b2 b1 b0
CH8CH7CH6CH5 CH4CH3CH2CH1
CH3: 0 (Enable)
CH1, CH2, CH4 to CH8: 1 (Disable)
11011111
Process alarm setting
b7 b6 b5 b4 b3 b2 b1 b0
CH8CH7CH6CH5 CH4CH3CH2CH1
CH2: 0 (Enable)
CH1, CH3 to CH8: 1 (Disable)