7 - 2
7.1 Online Module Change Conditions
7
ONLINE MODULE CHANGE
7.1 Online Module Change Conditions
The CPU, MELSECNET/H remote I/O module, Q68TD-G-H02(H01), GX Developer and
base unit given below are needed to perform an online module change.
(1) CPU
The Process CPU or Redundant CPU are required.
For precautions on multiple CPU system configuration, refer to the QCPU User's
Manual (Multiple CPU System).
For precautions on redundant system configuration, refer to the QnPRHCPU User's
Manual (Redundant System).
(2) MELSECNET/H remote I/O module
The module of function version D or later is necessary.
(3) GX Developer
GX Developer of Version 7.10L or later is necessary.
GX Developer of Version 8.18U or later is required to perform an online module
change on the remote I/O station.
(4) Base unit
(a) When the slim type main base unit (Q3 SB) is used, an online module change
cannot be performed.
(b) When the power supply module unnecessary type extension base unit (Q5 B) is
used, online module change cannot be performed for the modules on all the base
units connected.
Remark
The function version of the Q68TD-G-H02(H01) has been "C" from the first
release, supporting an online module change.