Mitsubishi Q68TD-G-H02 Thermometer User Manual


 
7 - 4
7.3 Online Module Change Procedure
7.3.1 When factory default is used and initial setting was made with GX Configurator-TI
7
ONLINE MODULE CHANGE
7.3 Online Module Change Procedure
(1) Procedures of online module change
There are the following online module change procedures depending on whether the
user range setting has been made or not, whether the initial setting of GX
Configurator-TI has been made or not, and whether the other system exists or not.
7.3.1 When factory default is used and initial setting was made with GX
Configurator-TI
(1) Conversion disable
(a) Set conversion enable/disable setting (Un\G0) for all channel conversion disable
and turn Operating Condition Setting Request (Y9) from OFF to ON to stop
conversion.
After confirming that conversion has stopped with the Conversion Completion
Flag (Un\G10), turn off Operating Condition Setting Request (Y9).
Figure 7.1 Device test screen
Table 7.2 Online module change procedures
Range setting Initial setting Other system Reference section
Factory setting GX Configurator-TI - Section 7.3.1
Factory setting Sequence program - Section 7.3.2
User range setting GX Configurator-TI Present Section 7.3.3
User range setting GX Configurator-TI Absent Section 7.3.4
User range setting Sequence program Present Section 7.3.5
User range setting Sequence program Absent Section 7.3.6