Setting
The following shows the setting elements for the frequency protection and their setting ranges.
Element Range Step Default Remarks
81-1 (L1, H1)
45.00 55.00Hz
(54.00 66.00Hz
0.01Hz
0.01Hz
49.00Hz
59.00Hz) (*)
Trip
81-2 (L2, H2)
45.00 55.00Hz
(54.00 66.00Hz
0.01Hz
0.01Hz
48.00Hz
58.00Hz)
Alarms
UV
40 100V
1V 40V Undervoltage block
TFRQL
0.00 60.00s
0.01s 10.00s Underfrequency trip time
delay
TFRQH
0.00 60.00s
0.01s 10.00s Overfrequency trip time
delay
TFRQA
0.00 60.00s
0.01s 10.00s Alarm time delay
Scheme switch
[FRQ-UF1]
[FRQ-UF2]
[FRQ1] to [FRQ5]
[FRQA]
Off/On
Off/On
Off/On
Off/On
On
On
(**)
On
Enable or disable
Trip
Alarm
Trip
Alarm
(*) : Frequency values shown in parentheses are for the case of 60Hz rating. Other frequency values
are shown for the case of 50Hz rating.
(**): Default settings are dependent on the models. See Appendix H.