Toshiba GRT100 Personal Lift User Manual


 
125
6 F 2 S 0 8 5 7
6.3 Preparations
Test equipment
The following test equipment is required for the commissioning tests.
1 Single-phase voltage source
2 Single-phase current sources
1 Variable-frequency source
1 Combined fundamental and 2nd-harmonic adjustable current supply
1 Combined fundamental and 5th-harmonic adjustable current supply
1 DC power supply
1 DC voltmeter
1 AC voltmeter
1 Phase angle meter
2 AC ammeters
1 Frequency meter
1 Time counter, precision timer
1 PC (not essential)
Relay settings
Before starting the tests, it must be specified whether the tests will use the user’s settings or the
default settings.
For the default settings, see the following appendixes:
Appendix D Binary Output Default Setting List
Appendix H Relay Setting Sheet
Visual inspection
After unpacking the product, check for any damage to the relay case. If there is any damage, the
internal module might also have been affected. Contact the vendor.
Relay ratings
Check that the items described on the nameplate on the front of the relay conform to the user’s
specification. The items are: relay type and model, AC voltage, current and frequency ratings, and
auxiliary DC supply voltage rating.
Local PC
When using a local PC, connect it with the relay via the RS-232C port on the front of the relay.
RSM100 software is required to run the PC.
For the details, see the separate instruction manual "PC INTERFACE RSM100".