LLNO class
Attribute Name Attr. Type Explanation T M/O GRT100
LNName Shall be inherited from Logical-Node Class (see IEC 61850-7-2)
Data
Common Logical Node Information
LN shall inherit all Mandatory Data from Common Logical Node Class
M
Loc SPS Local operation for complete logical device O Y
OpTmh INS Operation time O N
Controls
Diag SPC Run Diagnostics O Y
LEDRs SPC LED reset T O Y
PDIF class
Attribute Name Attr. Type Explanation T M/O GRT100
LNName Shall be inherited from Logical-Node Class (see IEC 61850-7-2)
Data
Common Logical Node Information
LN shall inherit all Mandatory Data from Common Logical Node Class
M
OpCntRs INC Resetable operation counter O N
Status Information
Str
A
CD Start M Y
Op
A
CT Operate T M Y
TmAst CSD
A
ctive curve charactristic O N
Measured Values
DifAClc WYE Differential Current O Y
RstA WYE Restraint Current O N
Settings
LinCapac
A
SG Line capacitance (for load currents) O N
LoSet ING Low operate value, percentage of the nominal current O N
HiSet ING High operate value, percentage of the nominal current O N
MinOpTmms ING Minimum Operate Time O N
MaxOpTmms ING Maximum Operate Time O N
RstMod ING Restraint Mode O N
RsDlTmms ING Reset Delay Time O N
TmACrv CURVE Operating Curve Type O N