Toshiba GRT100 Personal Lift User Manual


 
190
6 F 2 S 0 8 5 7
a-1 b-2
/3 Copy groupA to B (Active group= 1)
A ( 1- 8): _
B ( 1- 8):
/4 Protection (Group 8)
1=Transformer parameters
2=Trip
/4 Protection (Group 2)
1=Transformer parameter
2=Trip
/5 Transformer parameter (Group 1)
1=VT & CT ratio
/5 Trip (Group 1)
1=Phase matching
2=Scheme switch
3=Protection element
/2 Protection
1=Change active group
2=Change setting
3=Copy group
/4 Protection (Group 1)
1=Transformer parameter
2=Trip
/6 VT & CT ratio 1/ 7
1CT ( 1- 20000): 2000 _
2CT ( 1- 20000): 1000
3CT ( 1- 20000): 400
/3Change active group(Active group= *)
1=Group1 2=Group2 3=Group3 4=Group4
5=Group5 6=Group6 7=Group7 8=Group8
Current No.= * Select No.= _
/3 Change setting (Active group= *)
1=Group1 2=Group2 3=Group3 4=Group4
5=Group5 6=Group6 7=Group7 8=Group8
a-1 b-2 c-1
/6 Scheme switch 1/∗∗∗
DIFTPMD 1=3POR 2=1P 1 _
1REF 1=1IO 2=2IO 3=3IO 1
2REF 1=1IO 2=2IO 3=3IO 1
/6 Protection element (Group= 1)
1=DIFT 2=REF 3=OC
4=THR 5=V/F 6=FRQ
/7 OC 1/24
1OC ( 0.10- 20.00): 0.10 _ pu
2OC ( 0.10- 20.00): 0.10 pu
3OC ( 0.10- 20.00): 0.10 pu
/7 DIFT 1/13
ik ( 0.10- 1.00): 0.10 _ pu
p1 ( 10- 100): 10 %
p2 ( 10- 200): 100 %
/7 REF 1/21
1ik ( 0.05- 0.50): 0.05 _ pu
1kct1( 1.00- 50.00): 1.00
1kct2( 1.00- 50.00): 1.00
/7 THR 1/ 5
τ ( 0.5- 500.0): 0.5 _ min
k ( 0.10- 4.00): 0.10
IB ( 0.50- 2.50): 0.50 pu
/7 V/F 1/ 9
V ( 100.0- 120.0): 100.0_ V
A ( 1.03- 1.30): 1.10 pu
L ( 1.05- 1.30): 1.20 pu
/7 FRQ 1/ 6
81-1 ( 45.00- 55.00): 45.00_ Hz
81-2 ( 45.00- 55.00): 45.00 Hz
UV ( 40- 100): 40 V
/6 Phase matching
1=Alpha 2=Beta
Current No.=2 Select No. = _