INF Description Contents
GI Type COT FUN DPI
ID
Signal NO.
OFF ON
Fault Indications
64 Start/pick-up L1 A phase, A-B phase or C-A phase element pick-up No
65 Start/pick-up L2 B phase, A-B phase or B-C phase element pick-up No
66 Start/pick-up L3 C phase, B-C phase or C-A phase element pick-up No
67 Start/pick-up N Earth fault element pick-up No
68 General trip Any trip -- 2 1, 7 176 1280 -- 2
69 Trip L1 A phase, A-B phase or C-A phase trip No
70 Trip L2 B phase, A-B phase or B-C phase trip No
71 Trip L3 C phase, B-C phase or C-A phase trip No
72 Trip I>>(back-up) Back up trip Not supported
73 Fault location X In ohms
Fault location (prim. [ohm] / second. [ohm] / km
selectable by IECFL)
Not supported
74 Fault forward/line Forward fault Not supported
75 Fault reverse/Busbar Reverse fault Not supported
76
Teleprotection Signal
transmitted
Carrier signal sending Not supported
77 Teleprotection Signal received Carrier signal receiving Not supported
78 Zone1 Zone 1 trip Not supported
79 Zone2 Zone 2 trip Not supported
80 Zone3 Zone 3 trip Not supported
81 Zone4 Zone 4 trip Not supported
82 Zone5 Zone 5 trip Not supported
83 Zone6 Zone 6 trip Not supported
84 General Start/Pick-up Any elements pick-up No
85 Breaker Failure CBF trip or CBF retrip Not supported
86 Trip measuring system L1 No
87 Trip measuring system L2 No
88 Trip measuring system L3 No
89 Trip measuring system E No
90 Trip I> Inverse time OC trip No
91 Trip I>> Definite time OC trip No
92 Trip IN> Inverse time earth fault OC trip No
93 Trip IN>> Definite time earth fault OC trip No
Autoreclose indications
128 CB 'ON' by Autoreclose CB close command output Not supported
129
CB 'ON' by long-time
Autoreclose
Not supported
130 Autoreclose Blocked Autoreclose block Not supported