6 F 2 S 0 8 5 7
/4 Transformer parameter (Group 1)
1= VT & CT ratio
/4 Trip (Group 1)
1=Phase matching
2=Scheme switch
3=Protection element
/2 Protection (Active group= *)
1=Group1 2=Group2 3=Group3 4=Group4
5=Group5 6=Group6 7=Group7 8=Group8
/5 VT & CT ratio 3/ 4
1CT ( 2000 ) 2CT ( 1500 )
3CT ( 1500 ) 1nCT ( 1000 )
2nCT ( 500 ) 3nCT ( 2000 )
/3 Protection (Group 1)
1=Transformer parameter
2=Trip
/3 Protection (Group 8)
1=Transformer parameter
2=Trip
/3 Protection (Group 2)
1=Transformer parameter
2=Trip
a-1
a-1 b-1
/5 Protection element (Group 1)
1=DIFT 2=REF 3=OC
4=THR 5=V/F 6=FRQ
/6 OC 3/12
1OC ( 0.10 pu ) 2OC ( 0.10 pu )
3OC ( 0.10 pu ) T1OC ( 10.00 s )
T2OC ( 10.00 s ) T3OC ( 10.00 s )
/5 Scheme switch 3/∗∗∗
DIFTPMD 1=3POR 2=1P 1
1REF 1=1IO 2=2IO 3=3IO 1
2REF 1=1IO 2=2IO 3=3IO 1
/6 DIFT 3/ 7
ik ( 0.10 pu ) p1 ( 10 % )
p2 ( 50 % ) kp ( 1.00 pu )
kct1 ( 0.50 ) kct2 ( 0.50 )
/6 REF 3/11
1ik ( 0.50 pu ) 1kct1( 1.00 )
1kct2( 1.00 ) 1kct3( 1.00 )
1p2 ( 10 % ) 1kp ( 1.00pu )
/6 THR 3/ 3
τ ( 0.5 min) k ( 0.10 )
IB ( 1.00 pu ) lp ( 0.10 pu )
TA ( 0 min)
/6 V/F 3/ 5
V ( 100.0 V ) A ( 1.10 pu )
L ( 1.20 pu ) H ( 1.30 pu )
LT ( 1 s ) HT ( 3 s )
/6 FRQ 3/ 3
81-1 ( 45.00 Hz ) 81-2 ( 55.00 Hz )
UV ( 40 V ) TFRQL( 1.00 s )
TFRQH( 1.00 s ) TFRQA( 1.00 s )
/2 Binary output
1=IO#2 2=IO#3
/2 Binary input 3/16
BISW 1 1=Norm 2=Inv 1
BISW 2 1=Norm 2=Inv 1
BISW 3 1=Norm 2=Inv 1
/3 Binary output (IO#2) 3/13
BO1 ( 1, 100, 0, 0, 0, 0)AND,
BO2 ( 0, 0, 0, 0, 0, 0) OR,
BO3 ( 1, 2, 3, 4, 5, 6) OR,
/3 Binary output (IO#3) 3/10
BO1 ( 1, 100, 0, 0, 0, 0)AND,
BO2 ( 0, 0, 0, 0, 0, 0) OR,
BO3 ( 1, 2, 3, 4, 5, 6) OR,
/2 LED 3/ 4
LED1 ( 1, 309, 0, 0) AND,I
LED2 ( 0, 0, 0, 0) OR,I
LED3 ( 15, 16, 17, 0) OR,L
/5 Phase matching
1=Alpha 2=Beta
Current No.=2 Select No. = _