Toshiba GRT100 Personal Lift User Manual


 
280
6 F 2 S 0 8 5 7
IEC103 confi
g
urator Default settin
g
INF Description Contents
GI
Type
ID
COT FUN Max. No.
Measurands
144 Measurand I <meaurand I> No 0
145 Measurand I,V Ib1, Vab measurand <meaurand I> -- 3.2 2, 7 176 2
146 Measurand I,V,P,Q <meaurand I> No 0
147 Measurand IN,VEN <meaurand I> No 0
148
Measurand IL1,2,3, VL1,2,3,
P,Q,f
Ia1, Ib1, Ic1, f measurand <meaurand II> -- 9 2, 7 176 9
Generic Function
240 Read Headings Not supported
241
Read attributes of all entries
of a group
Not supported
243 Read directory of entry Not supported
244 Real attribute of entry Not supported
245 End of GGI Not supported
249 Write entry with confirm Not supported
250 Write entry with execute Not supported
251 Write entry aborted Not supported
Details of MEA settings in IEC103 configurator
INF MEA Tb1
Offset Data type Limit Co eff
Lower Upper
145 Ib1 1 28 short 0 4096 1.706666
Vab 1 12 short 0 4096 3.413333
148 Ia1 1 24 short 0 4096 1.706666
Ia2 1 28 short 0 4096 1.706666
Ia3 1 32 short 0 4096 1.706666
f 2 28 short 0 4096 0.0000833