Toshiba GRT100 Personal Lift User Manual


 
297
6 F 2 S 0 8 5 7
MMXN class
Attribute Name Attr. Type Explanation T M/O GRT100
LNName Shall be inherited from Logical-Node Class (see IEC 61850-7-2)
Data
Common Logical Node Information
LN shall inherit all Mandatory Data from Common Logical Node Class
M
EEHealth INS External equipment health (external sensor) O N
EEName DPL External equipment name plate O N
Measured values
A
mp MV Current I (rms) not allocated to a phase O N
Vol MV Voltage V (rms) not allocated to a phase O Y
Watt MV Power (P) not allocated to a phase O N
VolAmp
r
MV Reactive Power (Q) not allocated to a phase O N
VolAmp MV
A
pparent Power (S) not allocated to a phase O N
PwrFact MV Power Factor not allocated to a phase O N
Imp CMV Impedance O N
Hz MV Frequency O Y
MMXU class
Attribute Name Attr. Type Explanation T M/O GRT100
LNName Shall be inherited from Logical-Node Class (see IEC 61850-7-2)
Data
Common Logical Node Information
LN shall inherit all Mandatory Data from Common Logical Node Class
M
EEHealth INS External equipment health (external sensor) O N
Measured values
TotW MV Total Active Power (Total P) O N
TotVAr MV Total Reactive Power (Total Q) O N
TotVA MV Total Apparent Power (Total S) O N
TotPF MV
A
verage Power factor (Total PF) O N
Hz MV Frequency O N
PPV DEL Phase to phase voltages (VL1VL2, …) O N
PhV WYE Phase to ground voltages (VL1ER, …) O N
A
WYE Phase currents (IL1, IL2, IL3) O Y
W WYE Phase active power (P) O N
VA
r
WYE Phase reactive power (Q) O N
VA WYE Phase apparent power (S) O N
PF WYE Phase power factor O N
Z WYE Phase Impedance O N