Toshiba GRT100 Personal Lift User Manual


 
281
6 F 2 S 0 8 5 7
IEC103 Configurator Default setting
COM
Type
ID
COT FUN
Selection of standard information numbers in control direction
System functions
0
Initiation of general
interrogation
-- 7 9 255
0 Time synchronization -- 6 8 255
General commands
16 Auto-recloser on/off Not supported
17 Teleprotection on/off Not supported
18 Protection on/off (*1) ON/OFF 20 20 176
19 LED reset Reset indication of latched LEDs. ON 20 20 176
23 Activate characteristic 1 Setting Group 1 ON 20 20 176
24 Activate characteristic 2 Setting Group 2 ON 20 20 176
25 Activate characteristic 3 Setting Group 3 ON 20 20 176
26 Activate characteristic 4 Setting Group 4 ON 20 20 176
Generic functions
240
Read headings of all defined
groups
Not supported
241
Read values or attributes of all
entries of one group
Not supported
243
Read directory of a single
entry
Not supported
244
Read values or attributes of a
single entry
Not supported
245
General Interrogation of
generic data
Not supported
248 Write entry Not supported
249 Write entry with confirmation Not supported
250 Write entry with execution Not supported
INF Description Contents
(1) Note: While the relay receives the "Protection off" command, " IN SERVICE LED" is off.
Details of Command settings in IEC103 configurator
INF
DCO
Sig off Sig on
Rev Valid time
18 2686 2686 0
19 0 2688 200
23 0 2640 1000
24 0 2641 1000
25 0 2642 1000
26 0 2643 1000
: signal reverse