6 F 2 S 0 8 5 7
Default Setting of Relay Series(5A rating / 1A rating)
World wide ENA
2-Winding 3-Winding 3-Winding
5A rating 1A rating 101D 102D 201D 202D 203D 204D
214 V/F V 100.0 - 120.0
V Voltage 100.0 100.0
215 A 1.03 - 1.30
pu Alarm level 1.03 1.03
216 L 1.05 - 1.30
pu Low level 1.05 1.05
217 H 1.10 - 1.40
pu High level 1.40 1.40
218 LT 1 - 600
s
Inverce time delay for
high level
600 600
219 HT 1 - 600
s
Inverce time delay fir low
level
1 1
220 RT 60 - 3600
s
Radiant heat time 250 250
221 TVFH 1 - 600
s
Delay time for high level 10 10
222 TVFA 1 - 600
s
Delay time for alarm level 10 10
223 FRQ 81-1 45.00 - 55.00
Hz
Frequency-1 in 50Hz
rating
49.00 49.00
54.00 - 66.00
Hz
Frequency-1 in 60Hz
rating
59.00 59.00
224 81-2 45.00 - 55.00
Hz
Frequency-2 in 50Hz
rating
48.00 48.00
54.00 - 66.00
Hz
Frequency-2 in 60Hz
rating
58.00 58.00
225 UV 40 - 100
v Voltage 40 40
226 TFRQL 0.00 - 60.00
s
TRIP delay timer for low
level
10.0 10.0
227 TFRQH 0.00 - 60.00
s
TRIP delay timer for high
level
10.0 10.0
228 TFRQA 0.00 - 60.00
s
TRIP delay timer for alarm
level
10.0 10.0
229 BISW 1 Norm - Inv
Binary input Norm Norm
230 BISW 2 Norm - Inv
ditto Norm Norm
231 BISW 3 Norm - Inv
ditto Norm Norm
232 BISW 4 Norm - Inv
ditto Norm Norm
233 BISW 5 Norm - Inv
ditto Norm Norm
234 BISW 6 Norm - Inv
ditto Norm Norm
235 BISW 7 Norm - Inv
ditto Norm Norm
236 BISW 8 Norm - Inv
ditto Norm Norm
237 BISW 9 Norm - Inv
ditto Norm Norm
238 BISW 10 Norm - Inv
ditto Norm Norm
239 BISW 11 Norm - Inv
ditto Norm Norm
240 BISW 12 Norm - Inv
ditto Norm Norm
241 BISW 13 Norm - Inv
ditto Norm --
242 BISW 14 Norm - Inv
ditto Norm Norm
243 BISW 15 Norm - Inv
ditto Norm Norm
244 BISW 16 Norm - Inv
ditto Norm Norm
245 LED1 Logic OR - AND
Configurable
 
LEDs
OR OR
246 Reset Inst - Latch
Inst Inst
247 In #1 0 - 3071
0281
248 In #2 0 - 3071
00
249 In #3 0 - 3071
00
250 In #4 0 - 3071
00
251 LED2 Logic OR - AND
Configurable
 
LEDs
OR OR
252 Reset Inst - Latch
Inst Inst
253 In #1 0 - 3071
0291
254 In #2 0 - 3071
00
255 In #3 0 - 3071
00
256 In #4 0 - 3071
00
257 LED3 Logic OR - AND
Configurable
 
LEDs
OR OR
258 Reset Inst - Latch
Inst Inst
259 In #1 0 - 3071
0298
260 In #2 0 - 3071
00
261 In #3 0 - 3071
00
262 In #4 0 - 3071
00
263 LED4 Logic OR - AND
Configurable
 
LEDs
OR OR
264 Reset Inst - Latch
Inst Inst
265 In #1 0 - 3071
00
266 In #2 0 - 3071
00
267 In #3 0 - 3071
00
268 In #4 0 - 3071
00
269 Plant name Specified by user
Plant name no-name no-name
270 Description ditto
Memorandum for user no-data no-data
271 HDLC 1 - 32
Relay ID No. for RSM 1 1
272 IEC 0 - 254
Station address for
IEC103
22
273 SYADJ -9999 - 9999
ms Time sync. Compensation 0 0
274 IP1-1 0 - 254
IP Address of CH#1 192 192
275 IP1-2 0 - 254
168 168
276 IP1-3 0 - 254
19 19
277 IP1-4 0 - 254
172 172
278 SM1-1 0 - 255
Subnet Mask of CH#1 255 255
279 SM1-2 0 - 255
255 255
280 SM1-3 0 - 255
255 255
281 SM1-4 0 - 255
Subnet Mask of CH#1 0 0
282 GW1-1 0 - 254
192 192
283 GW1-2 0 - 254
168 168
284 GW1-3 0 - 254
19 19
285 GW1-4 0 - 254
11
Gateway Address of
CH#1
Contents
User
setting
Name
Range
Units