initiated and the following display appears. The input and output signals of the timer can be
observed at monitoring jacks A and B respectively. The LEDs above monitoring jacks A or B
are also lit if the input or output signal exists.
/2 Timer
Operating...
Press END to reset.
PressCANCELtocancel.
Press the
END
key to reset the input signal to the timer. The "TESTING" LED turns off.
Press the
CANCEL
key to test other timers. Repeat the above testing.
4.2.7.4 Logic Circuit
It is possible to observe the binary signal level on the signals listed in Appendix B with monitoring
jacks A and B.
Press 4 (= Logic circuit) on the "Test" screen to display the "Logic circuit" screen.
g
/
2 L o i c c i r c u i t 1
/
2
T e r m A ( 0 - 0 7 1 ) : 1 3
T e r m B
(
0- 071
)
:48
3
Enter a signal number to be observed at monitoring jack A and press the
ENTER
key.
Enter the other signal number to be observed at monitoring jack B and press the
ENTER
key.
After completing the setting, the signals can be observed by the binary logic level at monitoring
jacks A and B or by the LEDs above the jacks.
On screens other than the above screen, observation with the monitoring jacks is disabled.