Toshiba GRT100 Personal Lift User Manual


 
211
6 F 2 S 0 8 5 7
Default Setting of Relay Series(5A rating / 1A rating)
World wide ENA
2-Winding 3-Winding 3-Winding
5A rating 1A rating 101D 102D 201D 202D 203D 204D
146 DIFT ik 0.10 - 1.00 pu
Minimum operating
current
0.30 0.30
147 p1 10 - 100 %
% slope of small current
re
g
ion
100 100
148 p2 10 - 200 %
% slope of large current
re
g
ion
200 200
149 kp 1.00 - 20.00 pu
Break point of DIF
characteristic
1.00 1.00
150 kct1 0.05 - 50.00
CT ratio 1.00 1.00
151 kct2 0.05 - 50.00
ditto 1.00 1.00
152 kct3 0.05 - 50.00
ditto -- 1.00 1.00
153 d1 0 - 11
Phase an
g
le 0 0
154 d2 0 - 11
ditto 0 0
155 d3 0 - 11
ditto 0 0
156
y
d_p 1 - 2
Primar
y
windin
g
2 2
157
y
d_s 1 - 2
Secondar
y
windin
g
2 2
158 vec_s 0 - 11
Phase an
g
el
(
Secondar
y)
0 0
159
y
d_t 1 - 2
Tertiar
y
windin
g
-- 2 2
160 vec_t 0 - 11
Phase an
g
le
(
Tertiar
y)
-- 0 0
161 k2f 10 - 50 % 2f restraint 15 15
162 k5f 10 - 100 % 5f restraint 30 30
163 kh 2.00 - 20.00 pu HOC operain
g
current 2.00 2.00
164 REF 1ik 0.05 - 0.50 pu
Minimum sensitivity for
1REF
0.50 0.50
165 1kct1 1.00 - 50.00
CT ratio for 1REF 1.00 1.00
166 1kct2 1.00 - 50.00
ditto 1.00 1.00
167 1kct3 1.00 - 50.00
ditto -- 1.00 1.00
168 1p2 50 - 100 % Percent slope for 1REF 100 100
169 1kp 0.50 - 2.00 pu DF2 sensitivit
y
1.00 1.00
170 2ik 0.05 - 0.50 pu
Minimum sensitivity for
2REF
0.50 0.50
171 2kct1 1.00 - 50.00
CT ratio for 2REF 1.00 1.00
172 2kct2 1.00 - 50.00
ditto 1.00 1.00
173 2kct3 1.00 - 50.00
ditto -- 1.00 1.00
174 2p2 50 - 100 % Percent slope for 2REF 100 100
175 2kp 0.50 - 2.00 pu DF2 sensitivit
y
1.00 1.00
176 3ik 0.05 - 0.50 pu
Minimum sensitivity for
3REF
-- 0.50 0.50
177 3kct1 1.00 - 50.00
CT ratio for 3REF -- 1.00 1.00
178 3kct2 1.00 - 50.00
ditto -- 1.00 1.00
179 3kct3 1.00 - 50.00
ditto -- 1.00 1.00
180 3p2 50 - 100 % Percent slope for 3REF -- 100 100
181 3kp 0.50 - 2.00 pu DF2 sensitivit
y
-- 1.00 1.00
182 T1REF 0.00 - 10.00 s 1REF dela
y
trip timer 0.00 0.00
183 T2REF 0.00 - 10.00 s 2REF dela
y
trip timer 0.00 0.00
184 T3REF 0.00 - 10.00 s 3REF dela
y
trip timer -- 0.00 0.00
185 OC 1OC 0.10 - 20.00 pu OC element 2.00 2.00
186 2OC 0.10 - 20.00 pu ditto 2.00 2.00
187 3OC 0.10 - 20.00 pu ditto -- 2.00 2.00
188 T1OC 0.00 - 10.00 s OC dela
y
trip timer 1.00 1.00
189 T2OC 0.00 - 10.00 s ditto 1.00 1.00
190 T3OC 0.00 - 10.00 s ditto -- 1.00 1.00
191 1OCI 0.10 - 5.00 pu OCI element 1.00 1.00
192 2OCI 0.10 - 5.00 pu ditto 1.00 1.00
193 3OCI 0.10 - 5.00 pu ditto -- 1.00 1.00
194 T1OCI 0.05 - 1.00
OCI delayed tripping
timer
1.00 1.00
195 T2OCI 0.05 - 1.00
ditto 1.00 1.00
196 T3OCI 0.05 - 1.00
ditto -- 1.00 1.00
197 1EF 0.10 - 20.00 pu EF element 2.00 2.00
198 2EF 0.10 - 20.00 pu ditto 2.00 2.00
199 3EF 0.10 - 20.00 pu ditto -- 2.00 2.00
200 T1EF 0.00 - 10.00 s EF dela
y
trip time
r
1.00 1.00
201 T2EF 0.00 - 10.00 s ditto 1.00 1.00
202 T3EF 0.00 - 10.00 s ditto -- 1.00 1.00
203 1EFI 0.10 - 5.00 pu EFI element 1.00 1.00
204 2EFI 0.10 - 5.00 pu ditto 1.00 1.00
205 3EFI 0.10 - 5.00 pu dittp -- 1.00 1.00
206 T1EFI 0.05 - 1.00
EFI delayed tripping timer 1.00 1.00
207 T2EFI 0.05 - 1.00
ditto 1.00 1.00
208 T3EFI 0.05 - 1.00
ditto -- 1.00 1.00
209 THR t 0.5 - 500.0 min Time constant 60.0 60.0
210 k 0.10 - 4.00
Constant 1.30 1.30
211 IB 0.50 - 2.50 pu Basic current 1.00 1.00
212 Ip 0.00 - 1.00 pu Pre-load current 0.00 0.00
213 TA 0 - 10 min Time for alarmin
g
10 10
Contents
User
setting
Name
Range
Units