Appendix 2 Cable Manufacturing Drawings
2.3 R031 Cable (Analog signal input/output)
84
Cable type name: R031 cable Appendix 2.3
Application: Analog signal input/output
Assembly drawing
(1)(2)
(4)
(3)
R031
R031
Remote I/O unit side
Analog input/output signal
Connection diagram
2
1
12
11
3
5
13
15
7
FG
AI0
GND
AI1
GND
AI2
GND
AI3
GND
AO
GND
Remote I/O unit side
Analog input/output signal
Maximum cable length: 30m
Case frame
Manufacturing precautions
(1) The wire material shall be a shielded, 6-pair stranded cable equivalent to UL1061-2464
Standard AWG22 (0.3mm
2
).
(2) The parts used shall be Mitsubishi recommended parts. Equivalent parts may be used
providing they are compatible with the specifications.
(3) Attach the nameplate with protective cover stamped with the cable name in the position
designated in the assembly drawing.
(4) Fold the wire material shield on the remote I/O unit side over the sheath, and wrap copper foil
tape over it. Connect the copper foil tape wrapped around the sheath to a connector GND
plate.
(5) Stamp the name of each signal on the crimp terminal side mark tube and install.
(6) Insulate the crimp terminals of unused signal wires with vinyl tape, etc.
(7) Part 1 (plug) is usually used for wire material of AWG 24 (0.2mm
2
) or less in the catalog
specifications, but AWG 22 (0.3mm
2
) can also be used.
Option (compatible connector set)
FCUA-CS000
(Note that this is only compatible with the
remote I/O unit side.)
List of parts used
No. Part name Recommended part type Qty
1 Plug
Sumitomo 3M
10120-3000VE
1
2 Shell
Sumitomo 3M
10320-52F0-008
1
3
Wire
material
UL1061-2464
AWG22 × 6P
(1)
4
Crimp
terminal
J.S.T. Mfg
V1.25-4
10