7. Remote I/O Unit Connection (FCUA-DX1**)
7.4 Outline of Digital Signal Input Circuit
55
Input conditions
The input signals must be used within the following condition ranges.
Sink type
Input voltage at external contact ON 6V or less
Input current at external contact ON 9mA or more
Input voltage at external contact OFF 20V or more, 25.2V or less
Input current at external contact OFF 2mA or less
Tolerable chattering time (T1) 3ms or less
Input signal hold time (T2) 40ms or more
Input circuit operation delay time (T3, T4)
3ms T3
T4 16ms
Machine side contact capacity +30V or more, 16mA or more
Source type
Input voltage at external contact ON 18V or more, 25.2V or less
Input current at external contact ON 9mA or more
Input voltage at external contact OFF 4V or less
Input current at external contact OFF 2mA or less
Tolerable chattering time (T1) 3ms or less
Input signal hold time (T2) 40ms or more
Input circuit operation delay time (T3, T4)
3ms T3
T4 16ms
Machine side contact capacity +30V or more, 16mA or more
T2
T1 T1
T3
T4
T2
T1 T1
T3 T4
Sink type Source type