Emerson Rosemount 8732 Oxygen Equipment User Manual


 
Reference Manual
00809-0100-4665, Rev AA
August 2010
Rosemount 8732
3-10
NOTE
Be sure the calibration number reflects a calibration to a Rosemount
reference transmitter. If the calibration number was generated by a means
other than a certified Rosemount flow lab, accuracy of the system may be
compromised.
If your sensor is not a Rosemount sensor and was not calibrated at the
Rosemount factory, contact your Rosemount representative for assistance.
If your sensor is imprinted with an eight-digit number or a k-factor, check in
the sensor wiring compartment for the sixteen-digit calibration number. If
there is no serial number, contact the factory for a proper conversion.
Damping Adjustable between 0.0 and 256 seconds. This parameter is configured in the
Transducer Block.
Damping allows selection of a response time, in seconds, to a step change in
flow rate. It is most often used to smooth fluctuations in output.