Emerson Rosemount 8732 Oxygen Equipment User Manual


 
Reference Manual
00809-0100-4665, Rev AA
August 2010
E-17
Rosemount 8732
Series 2800 Sensor to
8732 Transmitter
Connect coil drive and electrode cables as shown in Figure E-14.
Figure E-14. Wiring Diagram for
Foxboro Series 2800 and
Rosemount 8732
Table E-15. Foxboro Series
2800 Sensor Wiring
Connections
ROSEMOUNT 8732
TRANSMITTER
Coil Connections
Electrode Connections
FOXBORO SERIES
1800 SENSOR
Outer Shield
White Lead
White Shield
Black Lead
Black Shield
Inner Shield
White
Black
Any Shield
L2
L1
Chassis Ground
Rosemount 8732 Foxboro Series 2800 Sensors
1 L1
2 L2
Chassis Ground
17 Any Shield
18 Black
19 White
This is a pulsed DC magnetic flowmeter.
Do not connect AC power to the sensor
or to terminals 1 and 2 of the
transmitter, or replacement of the
electronics board will be necessary.