Appendix G Transducer Block
Transducer Block Parameter Attribute Definitions . . . . . page G-1
TRANSDUCER BLOCK
PARAMETER
ATTRIBUTE
DEFINITIONS
The following table describes the parameters that are available in the
transducer block. Each line item in the table defines the element and specifies
the requirements for each element. If a column is blank for a data element, it
can be assumed that the column does not apply to that element.
Table G-1. Transducer Block
Parameters
Index Parameter Name Description
Profibus PA Specific Block Header
Information
16 BLOCK_OBJECT This object contains the characteristics of the
blocks.
17 ST_REV The modification of at least one static
parameter in a block has to be incremented
by the according ST_REV at least by one.
18 TAG_DESC Every block can be assigned a textual TAG
description. The TAG_DESC must be
unambiguous and unique in the fieldbus
system.
19 STRATEGY Grouping of Function Block. The STRATEGY
field can be used to group blocks.
20 ALERT_KEY This parameter contains the identification
number of the plant unit. It helps to
identify the location (plant unit) of an event.
21 TARGET_MODE The TARGET_MODE parameter contains
desired mode normally set by a control
application or an operator. The modes are
valid alternatively only, i.e. only one
mode can be set at one time. A write access
to this parameter with more then one mode is
out of the range of the parameter and have to
be refused.
22 MODE_BLK This parameter contains the current mode,
the permitted and normal mode of the block.
23 ALARM_SUM This parameter contains the current states of
the block alarms.
Magnetic Flow Meter Specific
Parameters
24 CALIBR_FACTOR This parameter is standard PA magnetic flow
parameter. Not used within 8732E device.