3.4.9 Averaging processing selection (Un\G24,Un\G25)
Averaging processing is selected for each channel.
(1) Setting methods
(a) The Averaging processing selection is set in the position corresponding to each
channel of buffer memory shown in the following figure.
Figure 3.27 Setting of Averaging processing selection (Un\G24,Un\G25)
(b) The following table shows the setting value.
(c) Turn on Operating condition setting request (Y9) to activate the setting.
(2) Default value
All channels are set to sampling processing (0000H).
[Setting example]
Set “0412
H” for Un\G24 as shown in the following figure in the case of the above
setting.
Figure 3.28 Setting example of Averaging processing selection (Un\G24,Un\G25)
POINT
If a value out of the setting range is set, sampling processing is performed.
Table 3.12 Processing method and setting value
Processing method Setting value
Samplling processing 0H
Time average 1H
Count average 2H
Moving average 3H
Primary delay filter 4H
CH1 Count average (2H)
CH2 Time average (1
H)
CH3 Primary delay filter (4
H)
CH4 Sampling processing (0
H)
b15 b12 b11 b8 b7 b4b3 b0
CH8 CH7 CH6 CH5
CH4 CH3 CH2 CH1
to
to
to to
Un\G24 (Averaging processing
selection CH1 to CH4)
Un\G25 (Averaging processing
selection CH5 to CH8)
Un\G24 (Averaging processing
selection CH1 to CH4)
b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0
0001001000000100